Hello. Can anyone try it on amd64? At this time I have only i386 and everything is OK on it.
On Tue, September 23, 2008 21:30, Thomas Pfaff wrote: > On Mon, 22 Sep 2008 23:24:25 +0400 (MSD) > "Kirill S. Bychkov" <[EMAIL PROTECTED]> wrote: > >> Hi. A lot of time has passed since my last attempt... >> This is the port of the latest version of apcupsd - APC UPS controlling >> software. >> Please, test and comment. > > gapcmon (-x11) crash on execution. > > apcupsd (-main and -cgi) works fine for me on amd64. > > $ apcaccess > APC : 001,044,1063 > DATE : Tue Sep 23 19:16:50 CEST 2008 > HOSTNAME : <snip> > RELEASE : 3.14.4 > VERSION : 3.14.4 (18 May 2008) openbsd > UPSNAME : <snip> > CABLE : USB Cable > MODEL : Back-UPS CS 650 > UPSMODE : Stand Alone > STARTTIME: Tue Sep 23 19:16:48 CEST 2008 > STATUS : ONLINE > LINEV : 238.0 Volts > LOADPCT : 36.0 Percent Load Capacity > BCHARGE : 100.0 Percent > TIMELEFT : 25.1 Minutes > MBATTCHG : 5 Percent > MINTIMEL : 3 Minutes > MAXTIME : 0 Seconds > OUTPUTV : 230.0 Volts > SENSE : High > DWAKE : 000 Seconds > DSHUTD : 000 Seconds > LOTRANS : 196.0 Volts > HITRANS : 256.0 Volts > RETPCT : 000.0 Percent > ITEMP : 29.2 C Internal > ALARMDEL : Always > BATTV : 13.4 Volts > LINEFREQ : 50.0 Hz > LASTXFER : Low line voltage > NUMXFERS : 0 > TONBATT : 0 seconds > CUMONBATT: 0 seconds > XOFFBATT : N/A > SELFTEST : NO > STATFLAG : 0x07000008 Status Flag > SERIALNO : QB0631237114 > BATTDATE : 2006-07-29 > NOMOUTV : 230 Volts > NOMINV : 230 Volts > NOMBATTV : 12.0 Volts > NOMPOWER : 400 Watts > FIRMWARE : 817.v4.I USB FW:v4 > APCMODEL : Back-UPS CS 650 > END APC : Tue Sep 23 19:17:01 CEST 2008 > > -- () ascii ribbon campaign - against html e-mail /\ www.asciiribbon.org - against proprietary attachments