Hearns, John <john.hearns <at> mclaren.com> writes: > > > > > i'm looking for, but have not found yet, a rear door heat exchanger > > with fans. the door should be able to support up to 35kw using > > chilled water. has anyone seen such an animal? > > > > most of the ones i've seen utilize a side car that sits beside the > > rack. unfortunately, i'm space limited and i need something that will > > hang on the back of the rack. > > SGI ICE clusters have chilled water rear doors just like that. > Four radiator sections which hinge out so you can access the rear of the > rack, > and you can keep the rack running while you hinge out one door at a > time. > No 'side car' cooling unit - you just couple it up to chilled water feed > and return via flexible pipes. > > Also check out CO2 cooling from Trox > http://www.troxaitcs.com/aitcs/products/CO2OLrac/index.html > > The contents of this email are confidential and for the exclusive use of the intended recipient. If you > receive this email in error you should not copy it, retransmit it, use it or disclose its contents but > should return it to the sender immediately and delete your copy. > Motivair Provides an active rear door "Chilled Door" providing 45kW with 65*F water. Motivair also manufactures a CDU for buildings with existing 45*F water supply.
http://www.motivaircorp.com/products/high-density-server-rack-cooling _______________________________________________ Beowulf mailing list, Beowulf@beowulf.org sponsored by Penguin Computing To change your subscription (digest mode or unsubscribe) visit http://www.beowulf.org/mailman/listinfo/beowulf